Technical data, General data and operating conditions – Lenze 8400 protec Manual User Manual

Page 40

Advertising
background image

Technical data

General data and operating conditions

4

l

40

EDS84DPS424 EN 5.0

Protection of persons and equipment

Enclosure

EN 60529

IP65

All unused connectors must be
closed with protection covers or
blanking plugs.

Deviating enclosure by
options:

IP64 with control element
C

IP54 with control element
W

IP55 with external fan for
7.5 kW devices

NEMA

Type 4X, indoor only

(Earth) leakage current

EN 61800−5−1

> 3.5 mA AC, > 10 mA DC

Observe the regulations and
safety instructions!

Total fault current

< 100 mA
Earth−leakage circuit breakers of type B can be used.

additional equipotential
bonding

M6 thread outside at the housing for connecting a 16mm

@ PE

cable

Protective insulation of
control circuits

EN 61800−5−1

Safe isolation from mains by double (reinforced) insulation

Insulation resistance

EN 61800−5−1

< 2000 m site altitude: Overvoltage category III

> 2000 m site altitude: Overvoltage category II

Short−circuit strength

EN 61800−5−1

Motor connection:
Limited, controller is inhibited, error acknowledgement
required

Phase/phase not
earth−fault−proof

Max. short−circuit current to be
expected: 10 kA

Motor holding brake
connection: no

Brake resistor connection:
no

PTC connection: not
earth−fault−proof

Control terminals: full

Protective measures for

l

Short circuit on the motor side at switchon and during
operation

l

Earth fault at switchon

l

Motor stalling

l

Motor overtemperature
– Input for PTC or thermal contact
– I

2

t monitoring

Cyclic mains switching

l

3 switching/minute

l

maximally 20 switching/hour

A circuit that can be reset automatically protects the device
against destruction.

Installation

EN 60204−1

Cable protection on the supply side is max. 32 A with

l

cable cross−section (L1, L2, L3): 6 mm

2

l

laying system B2

max. short−circuit current: < 10 kA