Overcurrent operation, Technical data – Lenze 8400 protec Manual User Manual

Page 56

Advertising
background image

Technical data

Overcurrent operation

4

l

56

EDS84DPS424 EN 5.0

4.4

Overcurrent operation

The controllers are designed for an overcurrent limited in time. The load due to defined,
cyclic operation is determined by the "Ixt" monitoring function. The "Ixt" function
comprises two moving averaging procedures which are checked in parallel:

ƒ

temporary moving averaging of the apparent motor current for pulse loads

ƒ

continuous moving averaging of the apparent motor current for permanent loads

Type of utilisation

Utilisation cycle

Monitoring function

Condition

Code

Pulse utilisation

15 s

I

aNx

> 160 %

l

Display in C00064/2

l

Display of the maximum
value in C00064/1

Permanent utilisation

180 s

The monitoring function is
permanently active.

l

Display in C00064/3

l

Display of the maximum
value in C00064/1

If the maximum value in code C00064/1 exceeds 100%, a "warning" will be generated or
a "trip" will be triggered (according to setting).