Operation at a rated mains voltage of 500 v, Technical data, 3 operation at a rated mains voltage of 500 v – Lenze 8400 protec Manual User Manual

Page 51

Advertising
background image

Technical data

Rated data

Operation at a rated mains voltage of 500 V

4

l

51

EDS84DPS424 EN 5.0

4.2.3

Operation at a rated mains voltage of 500 V

Basis of the data

Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

500

400 − 0 % ... 550 + 0 %

45 − 0 % ... 65 + 0 %

Mains current

Output power

Motor power

at I

arated

U, V, W

4 pol. ASM

Type

I

Lrated

[A]

S

arated

[kVA]

P

arated

[kW]

E84Dxxxx7514

3.2

1.5

0.75

E84Dxxxx1524

4.4

2.4

1.5

E84Dxxxx3024

7.9

4.6

3.0

E84Dxxxx4024

11.0

5.9

4.0

E84DHxxx7524

16.6

10.0

7.5

Output currents [A] at switching frequency

2 kHz

4 kHz

8 kHz

16 kHz

Type

I

arated2

I

aM2

I

arated4

I

aM4

I

arated8

I

aM8

I

arated16

I

aM16

E84Dxxx7514

1.9

4.8

1.9

4.4

1.9

4.4

1.3

3.1

E84Dxxx1524

3.1

7.8

3.1

7.2

3.1

7.2

1.7

3.4

E84Dxxx3024

5.8

14.6

5.8

13.5

5.8

13.5

3.9

7.4

E84Dxxx4024

7.6

19.0

7.6

17.6

7.6

13.4

5.1

7.3

E84DHxx7524

12.8

25.6

12.8

25.6

12.8

24.0

8.5

17.1

I

aNx

Rated value of continuous output current

I

aMx

Maximum output current (overload current)

l

Periodic load change of 3 s with I

aMx

and recovery time of 12 s according to

the tables under chapter

^ 4.4

l

Can be obtained in the setting "x kHz fixed/..." in C00018

Switching
frequency

If the maximum heatsink temperature is reached, the switching frequency is
reduced to 4 kHz.
In the setting "x kHz var./..." in C00018 the switching frequency is reduced
depending on the output current.
Depending on the switching frequency and e.g. the ambient temperature, it
may be required to reduce the output current (chapter 4.1, operating
conditions).

Advertising