Technical data

Current characteristics

4

l

54

EDS84DPS424 EN 5.0

4.3

Current characteristics

The controller limits its maximally possible motor current under the following operating
conditions ("current derating"):

ƒ

If the maximum heatsink temperature is exceeded
– In this case, the controller switches independently from switching frequency mode

of 16 kHz to 8 kHz and from 8 kHz to 4 kHz (but not from 4 kHz to 2 kHz). This
function can be deactivated via C00144.
When the heatsink temperature continues to rise, the inverter output will be
inhibited and the error message "Trip" occurs. This also occurs when the switching
frequency reduction is deactivated.

ƒ

In case of output frequencies f

out

< |5 Hz|

ƒ

As a function of the switching frequency modes "fixed" or "variable"

0

0

5

5

f

[Hz]

out

f

[Hz]

out

0

1

I

OUT

I

OUT

I

aM

I

aM

I

aM02

I

aM04

I

aM08

I

aM016

I

aM0v

I

aM2

I

aM4

I

aM8

I

aM16

I

aMv

8400GG084

Fig. 4−1

Current derating characteristics

0

Derating curve depending on the fixed switching frequency

1

Derating curve depending on the variable switching frequency

I

out

Output current

I

aM

Maximum output current (overload current)

I

aMx

Maximum output current (overload current) at different switching frequencies: 2kHz,
4kHz, 8kHz and 16kHz

I

aM0x

Maximum output current (overload current) at f

out

= 0Hz and different switching

frequencies: 2kHz, 4kHz, 8kHz, 16kHz

I

aMv

Maximum output current (overload current) at a variable switching frequency

I

aM0v

Maximum output current (overload current) at f

out

= 0Hz and a variable switching

frequency

f

out

Field frequency at the output U, V, W