Technical data, General data and operating conditions, Operating conditions – Lenze 8400 protec Manual User Manual

Page 41

Advertising
background image

Technical data

General data and operating conditions

4

l

41

EDS84DPS424 EN 5.0

Operating conditions

Ambient conditions

Climatic

Storage

EN 60721−3−1

1K3 (−25 ... +60 °C)

< 6 months

1K3 (−25 ... +60 °C)

> 6 months
> 2 years: Anodise DC bus
capacitors

Transport

EN 60721−3−2

2K3 (−25 ... +75 °C)

Operation

EN 60721−3−3

3K3 (−25 ... +55 °C)
"K" or "L" safety system included: −25 ... +45 °C

Operation at 2/4 kHz: > +45 °C: Reduce the rated output
current by 2.5 %/°C.
Operation at 8/16 kHz: > +40 °C: Reduce the rated output
current by 2.5 %/°C.

Site altitude

0 ... 4000 m amsl
Above 1000 ... 4000 m amsl: Reduce the rated output current
by 5 %/ 1000 m.

Pollution

EN 61800−5−1

Degree of pollution 2

Mechanical

Vibration resistance

(9.81 m/s

2

= 1 g)

Transport

EN 60721−3−2

2M2

EN 61800−2

2 ... 9 Hz: Amplitude 3.5 mm

10 ... 200 Hz: Acceleration resistant up to 10 m/s

2

200 ... 500 Hz: Acceleration resistant up to 15 m/s

2

Operation

Germanischer Lloyd

General conditions: Acceleration resistant up to 2 g

EN 60721−3−3

3M4

EN 61800−5−1

10 ... 57 Hz: Amplitude 0.075 mm

57 ... 150 Hz: Acceleration resistant up to 1 g

Supply conditions

Mains connection

Power system

TT, TN
(with earthed
neutral)

Operation is permitted without any restrictions.

IT

Only permitted with devices of voltage class "E" (see type
code).

Motor connection

Motors

EN 60034

Only use motors suitable for inverter operation. Insulation
resistance:
min. û

³1.5 kV, min. du/dt ³5 kV/ms

Length of the motor
cable

< 20 m (Lenze system cable, shielded)