Digital inputs and outputs

)

Note!

The maximum total current of the 24 V voltage supply for external actuators
and encoders is 1 A, e.g. ports

ƒ

Digital inputs/outputs at X4x,

ƒ

Analog input at X50 or SSI at X80, and

ƒ

Serial interfaces RS485/RS422 at X81/X82.

Digital inputs

X41 − digital inputs DI1, DI2

Pin

Signal

Description

Data

Type M12, 5−pole sockets

84DPSO05_5

1

24O

24 V supply of the external sensors

2

DI2

Digital input 2

According to IEC61131−2, type 1
or
Two−track frequency input for HTL
encoder 0 ... 100 kHz

3

GIO

Reference potential

HIGH
LOW

+15 .... +30 V DC
0 ... +5 V

4

DI1

Digital input 1

8 mA at 24 V DC

5

n. c.

Not assigned

X42 − digital inputs DI3, DI4

Pin

Signal

Description

Data

Type M12, 5−pole sockets

84DPSO05_5

1

24O

24 V supply of the external sensors

2

DI4
(DO2)

Digital input 4
(also available as digital output)

HIGH

+15 .... +30 V DC

3

GIO

Reference potential

LOW

0 ... +5 V

4

DI3
(DO1)

Digital input 3
(also available as digital output)

8 mA at 24 V DC

5

n. c.

Not assigned