Technical data

Rated data
Operation at rated mains voltage 400 V

4

l

50

EDS84DPS424 EN 5.0

Fuses and cable cross−sections

Operation without external mains choke/mains filter

Type

Installation according to EN 60204−1

1)

Installation according

to UL

2)

FI

3)



‚

L1, L2, L3 − Laying system

ƒ

L1, L2, L3

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E84Dxxxx7514

32

32

6

30

8

³ 300

E84Dxxxx1524

32

32

6

30

8

³ 300

E84Dxxxx3024

32

32

6

30

8

³ 300

E84Dxxxx4024

32

32

6

30

8

³ 300

E84DHxxx7524

32

32

6

30

8

³ 300

1)

These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298−4). The cable cross−sections apply under the following conditions: Use of PVC−insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.

2)

Use UL−approved cables, fuses and fuse holders only.
UL fuse: voltage

³ 500 V, tripping characteristic for example "H", "K5" or "CC". The cable cross−sections apply under

the following conditions: conductor temperature < 75 °C, ambient temperature < 45°C.

3)

Universal−current sensitive earth−leakage circuit breaker, short−time delay
If cables are longer than 50 m, the protective circuit−breaker may respond, depending on the cable type and
switching frequency.

 Circuit breaker

‚ Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category

ƒ Fuse
Observe national and regional regulations