Electrical installation − HighLine/StateLine version

Important notes
Electrical isolation

6

l

76

EDS84DPS424 EN 5.0

6.1.1

Electrical isolation

The protective insulation of the "8400 Inverter Drives" controllers is implemented
according to EN 61800−5−1. The following illustration shows the insulation concept.

X10

X11

X20

X21

X21

X3x

X4x

X50

X70

X80

X6x

X10

X11

(24 V)

(24 V)

(T1/T2)



‚

X22

X20

(T1/T2)

E84DWPT005

Fig. 6−1

Electrical isolation between power terminals, control terminals and housing

Isolation by functional insulation

I

Isolation by basic insulation

II

Safe isolation by double or reinforced insulation
Protection against accidental contact is guaranteed without any further
measures.



Power connections

X10, X11

Mains

X21

Motor

X20

Brake resistor

‚

Control terminals

X10 (24 V)
X11 (24 V)

24 V supply voltage

X20 (T1/T2)

brake resistor temperature monitoring

X21 (T1/T2)

Motor temperature monitoring

X22

Voltage supply of external fan − only for 7.5 kW devices

X3x

Fieldbus communication

X4x

Digital inputs/outputs

X50

Analog input

X6x

Safety system

X70

Diagnostics

X80

SSI

6.1.2

Device protection

ƒ

In case of condensation, do not connect the controller to the mains voltage before
the moisture has evaporated completely.

ƒ

The controller must be protected by external fuses.

ƒ

Unused control inputs and outputs must be closed according to the intended type of
protection.