Important notes

Maximum motor cable length

7

l

109

EDS84DPS424 EN 5.0

7.1.3

Maximum motor cable length

ƒ

Keep the motor cable as short as possible since this has a positive effect on the drive
behaviour.

ƒ

The maximally permissible motor cable length is: 20 m, shielded
– at rated mains voltage
– at a switching frequency of 8 kHz

)

Note!

If the conditions for electromagnetic compatibility must be observed, the
permissible cable lengths may vary.

7.1.4

Motor protection

ƒ

Extensive protection against overload:
– By overcurrent relays or temperature monitoring.
– We recommend the use of PTC thermistors or thermostats to monitor the motor

temperature.

– PTC thermistors or thermostats can be connected to the controller.
– For monitoring the motor, we recommend the use of the I

2

xt monitoring.

ƒ

Only use motors with an insulation suitable for the inverter operation:
– Insulation resistance: min. û = 1.5 kV, min. du/dt = 5 kV/

ms

– When using motors with an unknown insulation resistance, please contact your

motor supplier.