Electrical installation − ems version, Motor connection – Lenze 8400 protec Manual User Manual

Page 124

Advertising
background image

Electrical installation − EMS version

Devices in a power range of 0.75 ... 4 kW (3/PE AC 400 V)
Terminal assignment of the power connections

7

l

124

EDS84DPS424 EN 5.0

Motor connection

X21 − motor connection − device version E84DxxC...

Pin

Connection

Description

Data

1

2

3

4

5

6

7

8

+

Type Q8/0, sockets
Use Lenze system cable:

EYP0037xxxxxxxxQ10, 8−core, 1.5 mm

2

EYP0038xxxxxxxxQ11, 8 core, 2.5 mm

2

84DWTX0210

2

n. c.

Grooved pin as a protection against mix−up with power bus

1

U

Motor phase U

Max. 4 mm

2

Max. output voltage: mains voltage
Max. permanent output current:
type−dependent

3

W

Motor phase W

7

V

Motor phase V

4

BD2

Motor holding brake (reference
conductor)

Max. 4 mm

2

6

BD1

Motor holding brake

5

+PTC

Motor temperature monitoring

Max. 4 mm

2

PTC thermistor (PTC) or thermal
contact (NC contact)

8

−PTC

+

PE

PE conductor

Max. 4 mm

2

X21 − motor connection − device version E84DxxB...

Pin

Connection

Description

Data

Type Modular, sockets
Use Lenze system cable:

EYP0039xxxxxxxxQ08, 10−core, 1.5 mm

2

EYP0040xxxxxxxxQ09, 10−core, 2.5 mm

2

84DWTX0211

a1

U

Motor phase U

Max. 6 mm

2

Max. output voltage: mains voltage
Max. permanent output current:
type−dependent

a2

V

Motor phase V

a3

W

Motor phase W

c1

+PTC

Motor temperature monitoring

Max. 4 mm

2

PTC thermistor (PTC) or thermal
contact (NC contact)

c6

−PTC

c2

~

Supply voltage of brake rectifier

Max. 4 mm

2

V

rated

= mains voltage−dependent

The brake rectifier is mounted in the
terminal box of the motor.

c3

~

c4

S1

Switch for separation on the DC side

c5

S2

+

PE

PE conductor

Max. 6 mm

2

Advertising