Diagnostics – Lenze 8400 protec Manual User Manual

Page 166

Advertising
background image

Diagnostics

Display of operating data, diagnostics
Drive diagnostics via the integrated display

10

l

166

EDS84DPS424 EN 5.0

Message display

If warnings or errors are pending, their displays are blinking.

Overview of the error messages of the operating system

The table below lists all error messages of the controller operating system in alphabetically
ascending order of the abbreviated designation with the preset error response as well as
the parameter for setting the error response, if available.

Error

Group

ID Number

Abbr.

Text

Reaction

CAN code

Setting

106

1 0x0601

PL01

PLC internal

No reaction

C00596/1

2 0x0602

PL02

PLC watchdog

No reaction

C00596/2

3 0x0603

PL03

PLC parameter error

No Reaction

C00596/3

4 0x0604

PL04

PLC retain data error

No reaction

C00596/4

21 0x0615

PL21

PLC program generic error 1

No reaction

C00596/9

22 0x0616

PL22

PLC program generic error 2

No reaction

C00596/10

23 0x0617

PL23

PLC program generic error 3

No reaction

C00596/11

24 0x0618

PL24

PLC program generic error 4

No reaction

C00596/12

25 0x0619

PL25

PLC program generic error 5

No reaction

C00596/13

26 0x061a

PL26

PLC program generic error 6

No reaction

C00596/14

27 0x061b

PL27

PLC program generic error 7

No reaction

C00596/15

28 0x061c

PL28

PLC program generic error 8

No reaction

C00596/16

111

2 0x0b02

Su02

One mains phase is missing

Warning

0x3000

C00565

3 0x0b03

Su03

Too frequent mains switching

Fault

0x3000

4 0x0b04

Su04

CU supplied insufficiently

Fault

0x3000

5 0x0b05

Su05

IO supply overload

Warning

0x3000

C00598/4

119

50 0x1332

OC5

Ixt overload

Fault

0x2000

1 0x1301

OH1

Heatsink overtemperature

Fault

0x4000

15 0x130f

OH3

Motor temperature (X21) triggered

Fault

0x4000

C00585

0 0x1300

OH4

Heatsink temp. > shutdown temp. −5°C No reaction

0x4000

C00582