Lenze 8400 protec Manual User Manual
Page 107
Electrical installation − EMS version
Important notes
l
107
EDS84DPS424 EN 5.0
)
Note!
Only with the control element
ƒ
C = service switch with protective function
the device can be disconnected from the mains voltage.
)
Note!
The counter plugs of the power terminals must be equipped with connector
housings with a vertical outgoing cable.
)
Note!
ƒ
It is absolutely necessary to keep the plastic caps on the connectors for the
control terminals and interfaces!
ƒ
During transport, storage, and operation, ports not used must be sealed
using the plastic caps, in order to maintain the product features in
accordance with the technical data.
ƒ
Only if this note is observed, the product features certified are ensured for
devices with a safety system.
EMC−compliant wiring
)
Note!
ƒ
Establish a good conductive connection to protective earth by means of a
copper−braid cable (e.g. mounting surface, machine earth or building earth).
ƒ
Lay control cables and data lines separately from the motor cables.
ƒ
Connect the shields of the control cables and data lines at both ends.