Electrical isolation, Device protection, Electrical installation − ems version – Lenze 8400 protec Manual User Manual

Page 108

Advertising
background image

Electrical installation − EMS version

Important notes
Electrical isolation

7

l

108

EDS84DPS424 EN 5.0

7.1.1

Electrical isolation

The protective insulation of the "8400 Inverter Drives" controllers is implemented
according to EN 61800−5−1. The following illustration shows the insulation concept.

X10

X11

X20

X21

X21

X3x

X4x

X70

X8x

X10

(24 V)

(T1/T2)



‚

X50

E84DWPT006

Fig. 7−1

Electrical isolation between power terminals, control terminals and housing

Isolation by functional insulation

I

Isolation by basic insulation

II

Safe isolation by double or reinforced insulation
Protection against accidental contact is guaranteed without any further
measures.



Power terminals

X10, X11

Mains

X21

Motor

X20

Brake resistor

‚

Control terminals

X10 (24 V)

24 V supply voltage for the motor holding brake

X21 (T1/T2)

Motor temperature monitoring

X3x

Fieldbus communication, CAnopen Master PLC

X4x

Digital inputs/outputs

X50

Analog input

X70

Diagnostics

X8x

SSI, RS485/422

7.1.2

Device protection

ƒ

In case of condensation, do not connect the controller to the mains voltage before
the moisture has evaporated completely.

ƒ

The controller must be protected by external fuses.

ƒ

Unused control inputs and outputs must be closed according to the intended type of
protection.