External supply voltage 24 v, Technical data – Lenze 8400 protec Manual User Manual

Page 62

Advertising
background image

Technical data

Supply concept of control voltage
External supply voltage 24 V

4

l

62

EDS84DPS424 EN 5.0

4.6.2

External supply voltage 24 V

Detailed information on the X10 and X11 pin assignment with the external 24 V supply is
provided on page 87.

Example circuit

U24

=

+

-

X4x 24O

X11 GND

X10 GND

X11 24E

X10 24E

X62 24_ACK

int

+

-

1 A

E84D...

E84DVK003

X10 ...

External 24 V buffer voltage at the mains connection

X11 ...

External 24 V supply at the mains connection in loop−through technique
(for devices of the E84DxM... version)

X4x ...

24 V supply of the digital sensors

X62 ...

24 V supply of the safety system

U24

Internal 24 V supply

int

Voltage supply of the control electronics

An external 24 V supply voltage must comply with the following rated values to ensure
trouble−free operation of the controller.

X10

Pin / Name

Feature

Rated value

11 / 24E
12 / GND

Connection for external 24 V supply
voltage by a safely separated power
supply unit (required for feeding the
control electronics and the
communication module independent
of the mains supply)

24 V in accordance with IEC 61131−2
19.2 ... 28.8 V
Max. residual ripple

± 5 %

SELV/PELV

Suppression of voltage pulses

Suppressor diode 36 V, bidirectional

Electric strength of external voltage

+30 V

Excess current release

Automatically resettable

Polarity reversal protection

When polarity is reversed: No function and no
destruction

Current consumption

Approx. 0.6 A during operation if inputs/outputs are not
configured
Max. 2.0 A during operation with typical input/output
configuration
Max. 1.5 A starting current for 100 ms

Capacity to be charged

2000

mF

Max. load for plug contacts

10 A

Advertising