Technical data – Lenze 8400 protec Manual User Manual

Page 63

Advertising
background image

Technical data

Supply concept of control voltage

External supply voltage 24 V

4

l

63

EDS84DPS424 EN 5.0

X11

Pin / Name

Feature

Rated value

11 / 24E
12 / GND

Connection for an external 24 V
supply voltage (loop−through
arrangement)

24 V according to IEC 61131−2 (cp. X10)

Number of devices included in the
loop−through arrangement

is limited by the voltage drop due to max. current= 10 A
and max. cable cross−section = 2.5 mm

2

Max. load for plug contacts

10 A

X4x, X50/X8x

Pin / Name

Feature

Rated value

1 / 24O
3 / GIO

24 V supply of the external sensors or
potential−free contacts

External supply at 24E: voltage drop < 2.5 V
Internal supply: DC 18 ... 28 V

Max. output current

200 mA per output

Total current for X4x, X50/X8x

1 A

Electric strength of external voltage

+30 V

Excess current release

Automatically resettable