Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 101

Advertising
background image

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

101

CGCM Unit Configuration Chapter 4

Current Tab

The Current tab is used to configure the CGCM unit parameters related to the
over-current protection function.

Refer to

Appendix A

for more information on setting the parameters in the

Current tab as well as the available time over-current characteristic curves.

Over-current

Setpoint - Establishes the over-current threshold. When the generator

current exceeds this threshold, the CGCM unit starts timing toward a trip
based on the selected over-current curve, voltage-restraint setting, and time
dial setting. Tag Ovr_I_Setpt stores this parameter, expressed in percent
of rated generator current.

Over-current Curve - Selects the time over-current characteristic curve

that are used by the over-current function of the CGCM unit. Tag
Ovr_I_Curve

stores this parameter.

Over-current Time Dial – Selects a particular curve from the family of

curves contained in the selected over-current characteristic curve. Tag
Ovr_I_TimeDial

stores this parameter.

Over-current Voltage Restraint Setpoint - This setting establishes the

generator voltage threshold below which the CGCM unit automatically
reduces the selected time over-current setpoint. Tag Ovr_I_VrestSetpt
stores this value, expressed as a percent of rated generator voltage. The
over-current setpoint is reduced to the same percentage as the voltage
restraint threshold.