Loss of Operating Power Inputs to the CGCM Unit

• LossPMGFltOutEn - When this tag is a 1 in the configuration, and a Loss

of PMG Fault occurs the Fault Relay is energized. When this tag is a 0 in
the configuration, a Loss of PMG Condition has no effect on the Fault
Relay.

Loss of Operating Power Outputs from the CGCM Unit

• LossPMGFlt - This tag is used to communicate the occurrence of a Loss of

PMG Fault to the host Logix controller. When this tag is a 1, it indicates
that a fault has occurred. The tag is latched until the host Logix controller
resets it by setting the FltReset tag.

Reverse VAR Inputs to the CGCM Unit

• RevVARFltOutEn - When this tag is a 1 in the configuration, and a

Reverse VAR Fault occurs (as defined by the Rev_kVAR Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Over-voltage Condition has no effect on the Fault Relay.

• Rev_kVAR_Setpt - This tag configures the generator reverse kVAR

setpoint at which the CGCM unit recognizes a reverse kVAR (loss of
excitation) condition is present and starts timing to trip based on the
Reverse kVAR fault Delay setting.

• Rev_kVAR_TimeDly - This tag configures the time to

shutdown/annunciate once the generator reverse kVAR setpoint has been
exceeded.

Reverse VAR Outputs from the CGCM Unit

• RevVARFlt - This tag is used to communicate the occurrence of a Reverse

VAR Fault to the host Logix controller. When this tag is a 1, it indicates
that a fault has occurred. The tag is latched until the host Logix controller
resets it by setting the FltReset tag.

Definite Time Over-frequency Inputs to the CGCM Unit

• OvrFreqFltOutEn - When this tag is a 1 in the configuration, and an

Over-frequency Fault occurs (as defined by the OvrFreqSetpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Over-frequency Condition has no effect on the Fault Relay.

• OvrFreqSetpt - This tag configures the generator over-frequency setpoint

at which the CGCM unit recognizes an over-frequency condition is
present and starts timing to trip based on the Over-frequency Time Delay.

• OvrFreqTimeDly - This tag configures the time to shutdown/annunciate

once the generator Over-frequency Setpoint has been exceeded.