Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 84

Advertising
background image

84

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 4

CGCM Unit Configuration

Over-excitation Limiting Enable – Select this check box to enable

over-excitation limiting. Tag OEL_En in the configuration table stores
this parameter. In addition to selecting the check box, which sets the
OEL_En

tag in the configuration table, the OEL_En tag in the Output

(Scheduled Write) Data table must also be set to enable this function. In
Series B deices with firmware revision 3.3 or earlier, the OEL limiter
operates if either box is checked or the OEL_En tag in the Output
(Scheduled Write) Data table is set.

The tags listed below determine the points shown in the OEL

configuration diagrams below. These tags are in the configuration table
and are set by the like-named fields in the OEL tab. They are expressed as
amperes and seconds, respectively.

Figure 37 - Online OEL Configuration

Point A is defined by tags OEL_OnlineHiSetpt and
OEL_OnlineHiTimeDly

Point B is defined by OEL_OnlineMedSetpt and
OEL_OnlineMedTimeDly

Point C is defined by OEL_OnlineLoSetpt

Figure 38 - Offline OEL Configuration

Point D is defined by OEL_OfflineHiSetpt and
OEL_OfflineHiTimeDly

Point E is defined by OEL_OfflineLoSetpt

Online/Offline graph button - Toggles to show online or offline OEL

characteristics. The graph pictorially represents the OEL settings.

FIELD CURRENT

TIME IN SECONDS

High

Current

Time

0…10 seconds

CONTINUOUS

Medium

Current

Time

0…120 seconds

Low

Current

Level

0.0…15 A dc

Medium

Current

Level

0.0… 20 A dc

High

Current

Level

0.0…30 A dc

A

B

C

FIELD

C

URRENT

TIME IN SECONDS

High

Current

Time

CONTINUOUS

0…10 seconds

Low

Current

Level

0…15 A dc

High

Current

Level

0…30 A dc

D

E

Advertising