Limiting functions, Generator capability curve – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 50

Advertising
background image

50

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 3

CGCM Unit Operation

The tag SetptTraverseActive = 1 when the CGCM unit is traversing between
the internal tracking setpoint and the new operating mode's setpoint. The tag = 0
when the operating point has completed traversing to the new mode's setpoint.
This tag is used by the host Logix controller to determine when the new mode
has taken control.

Limiting Functions

This section discusses the different types of limiting functions the CGCM unit
provides.

Volts/Hertz Limit
Over-excitation Limit
Under-excitation Limit

Generator Capability Curve

The generator capability curve graphically depicts the combinations of real and
reactive power a generator is able to produce (or absorb, in the case of reactive
power) without damage caused by overheating. The CGCM unit provides a
number of limiting functions designed to maintain operation within safe areas of
the generator capability curve.

A typical generator capability curve is shown in the following illustration.

Figure 30 - Typical Generator Capability Curve

1.0

0.8

0.6

0.4

0.2

0.0

-0.2

-0.4

-0.6

-0.8

-1.0

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

Lagging

Leading

Reactive Power

, per Unit

Rating PF

Lagging

Armature Winding

Heating Limitation

Prime Mover

Power Limitation

95% PF

Leading

Armature Core

End Iron Heating

Limitation

Field Winding

Heating Limitation

Real Power, per Unit

Advertising