Troubleshooting

This chapter lists suggested diagnostic and corrective action procedures for a
variety of common generator system malfunctions. If the suggested actions do not
resolve the anomaly, please contact Rockwell Automation technical support.
Information on Rockwell Automation support can be found on the back cover.

This chapter does not include procedures to diagnose or correct issues related to
the basic communication between the CGCM unit and its host Logix controller.

For assistance in diagnosing ControlNet network communication issues, please
refer to ControlNet Coax Media Planning and Installation, publication

CNET-IN002

.

Table 19 - Excitation Control - FCR

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

No excitation current output

Excitation is not enabled

Check excitation enable (hardware

and software) and FCR select

Correct Logix controller logic or I/O

as required

Wiring error

Check wiring for excitation enable,

excitation current output, fuses

open, grounding, and PMG/supply

Correct wiring as required

No supply/PMG power

Measure Voltage at CGCM unit

PMG/supply input terminals

Correct supply anomaly if

insufficient voltage is measured

Excitation output is less than

setpoint

FCR not selected/enabled

Check excitation enable (hardware

and software) and FCR select

Correct Logix controller logic or I/O

as required

Wiring error

Check wiring for excitation enable,

excitation current output, fuses

open, grounding, and PMG/supply

Correct wiring as required

Insufficient supply power

Measure Voltage at CGCM unit

PMG/supply input terminals

Correct supply anomaly if

insufficient voltage is measured

Field resistance too great

Disconnect field current outputs at

CGCM unit and measure load

resistance

Correct/verify load resistance is

within CGCM unit capability

Gain mis-adjusted

Check gains entered into CGCM unit

configuration

Calculate/adjust as required