203

Specifications Appendix D

Loss of PMG

Reverse VAR

Over/Under-frequency

Reverse Power

Rotating Diode Monitor - Range

Attribute

1407-CGCM

Pickup

< 10V AC single-phase,

< 50V AC 3-phase or an imbalance
greater than 20%

Response time

< 400 ms

Attribute

Range

Increment

Accuracy

Time delay

0.10…300 s

0.10 s

±0.1 s

Attribute

Range

Increment

Accuracy

Pickup

30…70 Hz

0.01 Hz

±2% Hz

Time delay

0.10…300 s

0.10 s

±0.1 s

Attribute

Range

Increment

Accuracy

Pickup

1…100% of rated

generator VA

1%

±0.5% rated VA

Time delay

0.10…300 s

0.10 s

±0.1 s

Attribute

1407-CGCM

Number of generator poles

0…24

Number of brushless exciter poles

0…24

Increment

2

Fault time delay (applies to both open and

shorted diode conditions)

0.1…300 s