Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

159

Troubleshooting Chapter 7

Units do not share load equally: units

both change together

Series 2 CGCM unit on network is

powered down and load share lines

connected

Verify CGCM unit is firmware

revision earlier than 3.3

Replace with Series 3.x CGCM unit

when available

Add relay to disconnect load share

lines on power down

Load share full scale voltage

configurations do not match

Check full load voltage

configuration in each load share

device

Set full load voltage same in all load

share devices

Governor error

Check governor for use of LS

error from CGCM unit

Correct governor

Table 28 - Real Power Load Sharing

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

Table 29 - Synchronizing

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

No close indication from CGCM unit Phase not matched

Observe Phase match tag during

synchronization

If phase match indicated, check

close command tag. If no phase

match indicated, check phase match

error

Observe phase error reported by

CGCM unit during synchronization

If no phase error is reported by

CGCM unit, correct wiring and verify

appropriate Synchronization mode is

active
If phase error reported, verify

governor is responding to CGCM

unit reported error

Close output from CGCM unit not

being examined

Monitor Close breaker tag from

CGCM unit

If close indication received, check

use of tag. If no close indication,

check match errors

Frequency not matched

Observe frequency match tag during

synchronization

If frequency match indicated, check

close command tag. If no frequency

match indicated, check frequency

match error

Observe frequency error, generator

frequency, and selected bus

frequency reported by CGCM unit

during synchronization

If no frequency error is reported by

CGCM unit, correct wiring and verify

appropriate Synchronization mode is

active
If frequency error reported, verify

governor is responding to CGCM

unit reported error

Sync parameter configuration

incorrect

Observe configured synchronization

limits, VT input configuration, and

generator rated entries

Correct any errors in the

configuration entries