CGCM Unit Configuration Chapter 4

Related Parameters

Internal tracking – GenRatedExcI
Traverse rates – GenRated_V, GenRated_I, GenRatedExcI

Synch Tab

The Synch tab is used to configure the unit’s parameters related to the
synchronizing function of the CGCM unit.

Synchronization Limits

Frequency Match - Establishes the acceptance window for frequency

matching, defined by Configuration table tags SyncFreqLoLimit and
SyncFreqHiLimit

. These tags are set by using the Lower Limit and Upper

Limit fields in the Synch tab and are expressed in Hertz.

Voltage Match - Establishes the acceptance window for voltage matching,

defined by Configuration table tags SyncV_LoLimit and
SyncV_HiLimit

. These tags are set by using the Lower Limit and Upper

Limit fields in the Synch tab and are expressed in percent of rated
generator voltage.

Phase Match - Establishes the acceptance window for phase matching,

defined by Configuration table tags SyncPhLoLimit and
SyncPhHiLimit

. These tags are set by using the Lower Limit and Upper

Limit fields in the Synch tab and are expressed in degrees.