Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 198

Advertising
background image

198

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Appendix D

Specifications

Generator Voltage Sensing

Generator Current Sensing

Phase

Wiring
Configurations

Grounded
Connection
Available

Voltage Range for
Specified
Accuracy

Frequency Range
for Specified
Accuracy

Single-

phase

V Gen A and

V Gen C

No

Min 57 Vrms

Max 150 Vrms

Min 20 Hz

Max 90 Hz

Three-

phase

Floating wye

No

Min 99 Vrms L-L

Max 208 Vrms L-L

Min 20 Hz

Max 90 Hz

Three-

phase

Grounded wye

(grounded neutral)

Yes

Min 99 Vrms L-L

Max 208 Vrms L-L

Min 20 Hz

Max 90 Hz

Three-

phase

Open delta, grounded

B phase

Yes

Min 99 Vrms L-L

Max 208 Vrms L-L

Min 20 Hz

Max 90 Hz

IMPORTANT

Voltage sensing burden is < 1VA per phase.

TIP

For all wiring configurations, the minimum voltage sensing threshold is
2V AC typical. Maximum voltage withstand limit is 360V AC. These limits
are provided for reference only. Metering accuracy applies only when
operating in the range specified for voltage and frequency in the table
above for the specified wiring configuration.

Attribute

1407-CGCM

Type

3-phase plus cross current compensation input.

Frequency

50/60 Hz

Range

1 A or 5 A max continuous

Burden

< 0.1 VA per phase for metering CTs

< 2.5 VA per phase for cross-current inputs

Cross-current compensation entity parameters
ID(+) 1 A
ID(+) 5 A
ID(-)

Ui = 12 V
Ci = 14.1 nF
Ii = 5 AAC
Li = 1.5 µH