Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 4

CGCM Unit Configuration

Generator capability curve
Generator decrement curve

Consult with the generator manufacturer to be sure that you have the correct
data.

Record System Parameters

Verify and record system information and generator information required for
configuration of the CGCM unit. Typically this information can be obtained
from the generator nameplate, manufacturer’s data sheets, and system electrical
drawings.

Equipment Required

You need a suitable personal computer running RSLogix 5000 software. The
software is used to configure the CGCM unit for desired operation. RSLogix
5000 software contains a device profile that provides a user interface to the
CGCM unit configuration.

Refer to the CGCM Release Notes, publication

1407-RN001

, for information

on compatible RSLogix 5000 software versions and ControlLogix controller
firmware revisions.

Create a New Module in
the ControlLogix Controller

Follow these steps to create a new module in the ControlLogix controller with
RSLogix 5000 software.

1.

Under I/O Configuration, right-click 1756-CNB(R) and choose
New Module from the menu.

The Select Module Type dialog box appears. Add the CGCM unit as a
ControlNet module under the 1756-CNB(R) ControlNet Bridge module
in the controller.

IMPORTANT

You must be offline when you create a new module.