Definite Time Over-frequency Outputs from the CGCM Unit

• OvrFreqFlt - This tag is used to communicate the occurrence of an

Over-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.

Definite Time Under-frequency Inputs to the CGCM Unit

• UndrFreqFltOutEn - When this tag is a 1 in the configuration, and an

Under-frequency Fault occurs (as defined by the UndrFreqSetpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Under-frequency Condition has no effect on the Fault Relay.

• UndrFreqSetpt - This tag configures the generator under-frequency

setpoint at which the CGCM unit recognizes an under-frequency
condition is present and starts timing to trip based on the
Under-frequency Time Delay.

• UndrFreqTimeDly - This tag configures the time to

shutdown/annunciate once the generator Under-frequency Setpoint has
been exceeded.

• EngineIdle – Setting this tag to 1 disables the under-frequency,

under-voltage and Loss of PMG protections until the generator is at rated
speed.

Definite Time Under-frequency Outputs from CGCM

• UndrFreqFlt - This tag is used to communicate the occurrence of an

Under-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.

Reverse Power Protection Inputs to the CGCM Unit

• RevPwrFltOutEn - When this tag is a 1 in the configuration, and a

Reverse Power Fault occurs (as defined by the Rev_kW_Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, a
Reverse Power Condition has no effect on the Fault Relay.

• Rev_kW_Setpt - This tag configures the generator reverse kW setpoint at

which the CGCM unit recognizes a reverse power condition is present
and starts timing to trip based on the Reverse kW fault Delay setting.

• Rev_kW_TimeDly - This tag configures the time to

shutdown/annunciate once the generator reverse kW setpoint has been
exceeded.