Definite time under-frequency outputs from cgcm, Reverse power protection inputs to the cgcm unit – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 220
220
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Appendix E
Detailed CGCM Unit Tag Descriptions
Definite Time Over-frequency Outputs from the CGCM Unit
• OvrFreqFlt - This tag is used to communicate the occurrence of an
Over-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Definite Time Under-frequency Inputs to the CGCM Unit
• UndrFreqFltOutEn - When this tag is a 1 in the configuration, and an
Under-frequency Fault occurs (as defined by the UndrFreqSetpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Under-frequency Condition has no effect on the Fault Relay.
• UndrFreqSetpt - This tag configures the generator under-frequency
setpoint at which the CGCM unit recognizes an under-frequency
condition is present and starts timing to trip based on the
Under-frequency Time Delay.
• UndrFreqTimeDly - This tag configures the time to
shutdown/annunciate once the generator Under-frequency Setpoint has
been exceeded.
• EngineIdle – Setting this tag to 1 disables the under-frequency,
under-voltage and Loss of PMG protections until the generator is at rated
speed.
Definite Time Under-frequency Outputs from CGCM
• UndrFreqFlt - This tag is used to communicate the occurrence of an
Under-frequency Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.
Reverse Power Protection Inputs to the CGCM Unit
• RevPwrFltOutEn - When this tag is a 1 in the configuration, and a
Reverse Power Fault occurs (as defined by the Rev_kW_Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, a
Reverse Power Condition has no effect on the Fault Relay.
• Rev_kW_Setpt - This tag configures the generator reverse kW setpoint at
which the CGCM unit recognizes a reverse power condition is present
and starts timing to trip based on the Reverse kW fault Delay setting.
• Rev_kW_TimeDly - This tag configures the time to
shutdown/annunciate once the generator reverse kW setpoint has been
exceeded.