Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 16

Advertising
background image

16

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 2

Installation

TB3

2.6…2.1 mm

2

(10…12 AWG)

ID(+)1 A

1 A cross-current compensation CT input

ID(+)5 A

5 A cross-current compensation CT input

ID(-)

Cross-current compensation CT common input

I3(+)1 A

1 A phase C CT input

I3(+)5 A

5 A phase C CT input

I3(-)

Phase C CT common input

I2(+)1 A

1 A phase B CT input

I2(+)5 A

5 A phase B CT input

I2(-)

Phase B CT common input

I1(+)1 A

1 A phase A CT input

I1(+)5 A

1 A phase A CT input

I1(-)

Phase A CT common input

TB4

1.6…1.0 mm

2

(14…18 AWG)

BAT(+)

24V DC control power input

BAT(-)

24V DC control power return

FLT

Open collector fault output

RD RLY

Open collector output for redundancy relay

CH GND

Chassis ground

TB5

V Gen A

Phase A generator voltage input

V Gen B

Phase B generator voltage input

V Gen C

Phase C generator voltage input

V Gen N

Neutral generator voltage input

TB6

V Bus A

Phase A bus voltage input

(1)

V Bus B

Phase B bus voltage input

(1)

V Bus C

Phase C bus voltage input

V Bus N

Neutral bus voltage input

TB7

1.6…1.0 mm

2

(14…18 AWG)

VREF(+)

Remote setpoint adjust input

VREF(-)

Remote setpoint adjust input return

SHLD3

Shield 3 landing points are tied together but are not connected internally to protective earth or

other unit circuitry

SHLD3
A-COM

Analog common

EX-D(+)

Excitation enable input

EX-D(-)

Excitation enable return

LS(+)

Real power load sharing input

LS(-)

Real power load sharing return

SHLD4

Shield 4 landing point is not connected internally to protective earth or other unit circuitry

(1) When used in a dual breaker configuration, Bus A voltage input is wired from V Bus A to V Bus N and Bus B is wired from V Bus B to V Bus N.

Table 1 - Terminal Block Label Description

Terminal Block

Wire Gauge
Range

Label

Description