Synchronizing outputs from the cgcm unit – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 224

Advertising
background image

224

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Appendix E

Detailed CGCM Unit Tag Descriptions

• BusA_PhOffset - This tag configures a phase angle added to the measured

bus A phase angle. It is used to compensate for phase shift across sensing
transformers.

• BusA_V_Scaler - This tag configures a multiplier by which the measured

bus A voltage is multiplied. It is used to compensate for ratio error across
sensing transformers.

• BusB_PhOffset - This tag configures a phase angle added to the measured

bus B phase angle. It is used to compensate for phase shift across sensing
transformers.

• BusB_V_Scaler - This tag configures a multiplier by which the measured

bus B voltage is multiplied. It is used to compensate for ratio error across
sensing transformers.

• BusA_B_Select – This tag selects which reference bus the CGCM unit

attempts to synchronize to.

• V_Match Gain-This tag sets the Proportional Gain parameter for Voltage

Matching mode

Synchronizing Outputs from the CGCM Unit

• SyncDeadBus - This tag indicates all conditions have been to allow a

DeadBus synchronization

• AutoSync – This tag follows the AutoSyncEn tag setting in the Scheduled

Write tag.

• CheckSync - This tag follows the CheckSyncEn tag setting in the

Scheduled Write tag.

• PermissiveSync - This tag follows the PermissiveSyncEn tag setting in the

Scheduled Write tag.

• SyncFailure – This tag indicates that the synchronization attempt failed.
• UndefinedSyncMode – This tag indicates that a synchronization was

initiated when none of the synchronization modes were asserted.

• SyncModeConflict – This tag indicates that more than one

Synchronization mode was selected.

• BusRot_ABC_ACB – This tag reports the rotation sequence of the

reference bus in three phase metering. In single phase metering, these bits
reflect the configuration value.

• GenRot_ABC_ACB – This tag reports the rotation sequence of the

generator bus in three phase metering. In single phase metering, these bits
reflect the configuration value.

• PhRotMatch – This tag reports that the phase rotation between the two

busses to be synchronized matches, and is acceptable for synchronizing.

• V_Match - This tag reports that the voltage difference between the two

busses is within the configured acceptable range.

• FreqMatch - This tag reports that the frequency difference between the

two busses is within the configured acceptable range.

Advertising