Soft start control – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 190

Advertising
background image

190

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Appendix B

CGCM Unit Math Models

Soft Start Control

The soft start control function is provided to cause orderly build-up of terminal
voltage from the residual voltage to the rated voltage in desired time with
minimal overshoot. In CGCM units, the fast dynamic response is used while the
voltage reference is adjusted based on the elapsed time. When the system is under
start-up condition, the voltage reference is adjusted by the amount calculated
based on two programmable parameters, initial soft start voltage level (V

O

) and

desired time (T

SS

) to build up to the rated voltage. Its mathematical model is

shown in Soft Start Control. The soft start gain (K

SS

) is calculated by using this

formula.

K

SS

= (V

REF

- V

O

) / T

SS

Figure 68 - Soft Start Control