Detailed CGCM Unit Tag Descriptions Appendix E

Line-drop Compensation Inputs to the CGCM Unit

• LineDropComp - This tag configures the amount of voltage droop that is

experienced during paralleling generator applications.

Under-excitation Limit Inputs to the CGCM Unit

• UEL_En - Setting this tag enables the Under-excitation Limiting

function.

• UEL_Kg - This tag lets you adjust the proportional gain of the

Under-excitation limiter. It also determines the response of the limiter to
an Under-excitation event. Increasing this term increases the speed of the
response of the limiter.

• UEL_Ki - This tag lets you adjust coarse loop gain and overall gain of the

Under-excitation limiter. This tag determines the characteristic of the
dynamic response to an Under-excitation event.

• UEL_Curve_W_Pt1 – This tag is used as the Watt coordinate in the first

Watt, VAR coordinate pair, that, in combination with four other Watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.

• UEL_Curve_W_Pt2 – This tag is used as the Watt coordinate in the

second Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.

• UEL_Curve_W_Pt3 - This tag is used as the Watt coordinate in the third

Watt, VAR coordinate pair, that, in combination with four other Watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.

• UEL_Curve_W_Pt4 - This tag is used as the Watt coordinate in the

fourth Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.

• UEL_Curve_W_Pt5 - This tag is used as the Watt coordinate in the fifth

Watt, VAR coordinate pair, that, in combination with four other Watt,
VAR coordinate pairs, lets you enter an Under-excitation Limiting curve.

• UEL_Curve_VAR_Pt1 - This tag is used as the VAR coordinate in the

first Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.

• UEL_Curve_VAR_Pt2 - This tag is used as the VAR coordinate in the

second Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.

• UEL_Curve_VAR_Pt3 - This tag is used as the VAR coordinate in the

third Watt, VAR coordinate pair, that, in combination with four other
Watt, VAR coordinate pairs, lets you enter an Under-excitation Limiting
curve.