Voltage regulator – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 186

Advertising
background image

186

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Appendix B

CGCM Unit Math Models

Voltage Regulator

The

Per-unit Block Diagram for Rotating Rectifier Excitation System

shows the

model of the CGCM excitation system used with a brush-type rotating exciter.

The rotating exciter parameters are not included in this discussion because they
are the responsibility of the exciter manufacturer. V

P

is the input from the power

source for the excitation system.

A typical value for T

A

is 0. The forcing limit V

RLMT

is related to the power-input

voltage (V

P

) to the CGCM and the exciter field voltage (V

R

) as follows:

V

RLMT

= 1.4*V

P

/ V

R

The gain K

G

is used for compensating variations in system configuration such as

power input voltage. The per unit base of the parameters V

P

and V

R

is the

nominal exciter field voltage at no load.

The PID gains K

P

, K

I

, and K

D

are custom designed for the best performance for

each generator/exciter system. These continuous time gains are changed to
discrete and implemented in the CGCM digital controller. The PID gains can be
obtained from the PID Calculator software available from Rockwell
Automation.

Figure 60 - Per-unit Block Diagram for Rotating Rectifier Excitation System

V

RLMT

/(V

p

0.005)

-V

RLMT

/(V

p

0.005)

Advertising