Chapter 7

Troubleshooting

Excitation output is greater than

setpoint

FCR not selected/enabled

Check excitation FCR select

Correct Logix controller logic or I/O

as required

Wiring error

Check wiring for excitation current

output, fuses open, grounding, and

PMG/supply

Correct wiring as required

Gain mis-adjusted

Check gains entered into CGCM unit

configuration

Calculate/adjust as required

Excitation is erratic/unstable

Gain mis-adjusted

Check gains entered into CGCM unit

configuration

Calculate/adjust as required

Wiring error

Check wiring for excitation enable,

excitation current output, fuses

open, grounding, and PMG/supply

Correct wiring as required

Table 19 - Excitation Control - FCR

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

Table 20 - Excitation Control - AVR

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

No excitation current output

Excitation is not enabled

Check excitation enable (hardware

and software) and AVR select

Correct Logix controller logic or I/O

as required

Wiring error

Check wiring for excitation enable,

excitation current output, VT inputs,

fuses open, grounding, and

PMG/supply

Correct wiring as required

No supply/PMG power

Measure Voltage at CGCM unit

PMG / supply input terminals

Correct supply anomaly if

insufficient voltage is measured