Detailed CGCM Unit Tag Descriptions

Over-excitation Limit Inputs to the CGCM Unit

• OEL_En – Setting this tag enables the Over-excitation Limiting function.
• OEL_Kg - This tag lets you adjust the proportional gain of the

Over-excitation limiter. It also determines the response of the limiter to an
Over-excitation event.

• OEL_Ki - This tag lets you adjust coarse loop gain and overall gain of the

Over-excitation limiter. This tag determines the characteristic of the
dynamic response to an Over-excitation event.

• OEL_OnLineHiSetpt – This tag sets the high current level for the online

over-excitation limiting function. The CGCM unit’s over-excitation
limiter limits excitation current at this level. Operation at this level is
allowed for a time no longer than programmed in the
OEL_OnLineHiTimeDly tag.

• OEL_OnLineHiTimeDly – This tag sets the amount of time the online

over-excitation limiting function lets the unit operate at the excitation
current level programmed in the OEL_OnLineHiSetpt tag.

• OEL_OnLineMedSetpt -

This tag sets the medium current level for the

online over-excitation limiting function. Operation at this level is allowed
for a time no longer than programmed in the OEL_OnLineMedTimeDly
tag.

• OEL_OnLineMedTimeDly – This tag sets the amount of time the online

over-excitation limiting function lets the unit operate at the excitation
current level programmed in the OEL_OnLineMedSetpt tag.

• OEL_OnLineLoSetpt -

This tag sets the low current level for the online

over-excitation limiting function. Operation at this level is allowed
continuously.

• OEL_Off LineHiSetpt – This tag sets the high current level for the

offline over-excitation limiting function. The CGCM unit’s
over-excitation limiter limits excitation current at this level. Operation at
this level is allowed for a time no longer than programmed in the
OEL_OffLineHiTimeDly tag.

• OEL_Off LineHiTimeDly - This tag sets the amount of time the offline

over-excitation limiting function lets the unit operate at the excitation
current level programmed in the OEL_OffLineHiSetpt tag.

• OEL_Off LineLoSetpt - This tag sets the low current level for the offline

over-excitation limiting function. Operation at this level is allowed
continuously.

Over-excitation Limit Outputs from the CGCM Unit

• OEL_Active – This tag is set to 1 when the exciter is operating in the

Over-excitation Limiting mode.