Metered parameter accuracy – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 65

Advertising
background image

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

65

CGCM Unit Operation Chapter 3

Table 3 - Metered Parameter Accuracy

Metered Parameter

Metering Wiring Mode

Single-phase

Delta

Three-wire Wye

Four-wire Wye

Dual-bus

Gen Voltages, 3, L-L

CA

AB, BC, CA

AB, BC, CA

AB, BC, CA

-

Gen Voltage, avg, L-L

Yes (=CA)

Yes

Yes

Yes

-

Gen Voltages, 3, L-N

N/A

N/A

N/A

A, B, C

-

Gen Voltage, avg, L-N

N/A

N/A

N/A

Yes

-

Gen Currents, 3

A, B, C

A, B, C

A, B, C

A, B, C

-

Gen Current, avg

Yes

Yes

Yes

Yes

-

Gen Kilowatts, 3

N/A

N/A

N/A

A, B, C

-

Gen Kilowatts, total

Yes

Yes

Yes

Yes

-

Gen kVA, 3

N/A

N/A

N/A

A, B, C

-

Gen kVA, total

Yes

Yes

Yes

Yes

-

Gen kVAR, 3

N/A

N/A

N/A

A, B, C

-

Gen kVAR, total

Yes

Yes

Yes

Yes

-

Gen Power Factor, 3

N/A

N/A

N/A

A, B, C

-

Gen Power Factor, avg

Yes

Yes

Yes

Yes

-

Gen Frequency

Yes

Yes

Yes

Yes

-

Excitation Current

Yes

Yes

Yes

Yes

-

Gen Kilowatt Hours

Yes

Yes

Yes

Yes

-

Gen kVAR Hours

Yes

Yes

Yes

Yes

-

Gen kVA Hours

Yes

Yes

Yes

Yes

-

Diode Ripple Level

Yes

Yes

Yes

Yes

-

Load Share Error

Yes

Yes

Yes

Yes

-

Voltage Match Error

(1)

(1)

(1)

(1)

(1)

Sync Phase Error

(1)

(1)

(1)

(1)

(1)

Sync Frequency Error

(1)

(1)

(1)

(1)

(1)

Bus Voltages, 3, L-L

CA

AB, BC, CA

AB, BC, CA

AB, BC, CA

N/A

Bus Voltage, avg, L-L

Yes (=CA)

Yes

Yes

Yes

Yes

Bus Voltages, 3, L-N

N/A

N/A

N/A

A, B, C

N/A

Bus Voltage, avg, L-N

N/A

N/A

N/A

Yes

N/A

Bus A Frequency

Yes

Yes

Yes

Yes

Yes

Bus B Frequency

N/A

N/A

N/A

N/A

Yes

Gen Phase Rotation

N/A

Yes

Yes

Yes

Yes

Bus Phase Rotation

N/A

Yes

Yes

Yes

N/A

(1) Results updated only while Synchronization is active (tag InitiateSync = 1).