Internal Tracking

Enable internal tracking - This checkbox sets the Boolean tag

Internal_Tracking_En

in the Configuration data table. When the value

of this tag is 1, internal tracking between voltage regulating modes is
enabled and the Traverse Rates are enabled. If the tag value is 0, both the
Traverse Rates and tracking between regulation modes is disable.

Internal Tracking Rate - This setting changes the rate at which the internal

tracking function matches the non-active excitation control modes to the
active excitation control mode. This sets the value of the
InternalTrackRate

tag in the Configuration table, expressed in seconds.

Internal Tracking Delay - This setting adjusts the delay in the internal

tracking function. This sets the value of the InternalTrackDelay tag in the
Configuration table, expressed in seconds. Its purpose is to reduce the
likelihood that the short-term response of the active regulating mode to an
upset is transferred to a new mode of operation when the mode is
switched. If the internal tracking delay is too short, the transient response
to an upset is transferred to the new operating mode. Conversely, if the
tracking delay is set too long, there is a risk of an old operating point being
transferred to the new operating mode, resulting in an undesirable bump.

An example of how these parameters affect tracking is shown in the

Internal

Tracking

graph. In this example, a loss of sensing causes a full-scale regulator

output. The internal tracking delay permits FCR mode to begin operation at the
output level prior to the loss of sensing.

Figure 39 - Internal Tracking

<

Setpoint / Regulator Output

AVR Setpoint

Regulator

Output

Internal

Tracking

Internal

Tracking Delay

Internal Tracking

Delay

Internal Tracking

Delay

4x Internal

Tracking Delay

FCR

Setpoint

Upset

Mode Switched

to FCR

Rapid Decline to

Tracked Value

Return from Tracked

Value to FCR Setpoint

Time