Data table – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 142

Advertising
background image

142

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 6

CGCM Unit Software Interface

Data Table

Although the Unscheduled Write tag is contained in the Configuration tag in the
Logix controller tags, the Unscheduled Write must be read back from the
CGCM unit independently.

Message size depends on the unit’s firmware revision. 64 (FRN 2.

x) or 76 (FRN

3.

x or later) byte Message size from CNET to CGCM (Written to the CGCM

unit).

Table 15 - Unscheduled Write Data Table, Assembly Instance 6

Byte

Size in
Bytes

Type

Tag Name

Description

Units

Range

Error
Code

0

4

Real

LineDropComp

Line Drop Compensation

%

0…10

1

4

4

Real

AVR_FCR_Kp

Automatic Voltage Regulator/Field Current

Regulator Proportional Gain

-

0…1000

2

8

4

Real

AVR_FCR_Ki

Automatic Voltage Regulator/Field Current

Regulator Integral Gain

-

0…1000

3

12

4

Real

AVR_FCR_Kd

Automatic Voltage Regulator/Field Current

Regulator Derivative Gain

-

0…1000

4

16

4

Real

AVR_FCR_Td

Automatic Voltage Regulator/Field Current

Regulator Derivative Time Constant

-

0…1000

5

20

4

Real

AVR_Kg

Automatic Voltage Regulator Overall Gain

-

0…1000

6

24

4

Real

FCR_Kg

Field Current Regulator Overall Gain

-

0…1000

7

28

4

Real

PF_Kg

Power Factor Overall Gain

-

0…1000

8

32

4

Real

PF_Ki

Power Factor Integral Gain

-

0…1000

9

36

4

Real

VAR_Kg

VAR Overall Gain

-

0…1000

10

40

4

Real

VAR_Ki

VAR Integral Gain

-

0…1000

11

44

4

Real

OEL_Kg

Over-excitation Limiting Overall Gain

-

0…1000

12

48

4

Real

OEL_Ki

Over-excitation Limiting Integral Gain

-

0…1000

13

52

4

Real

UEL_Kg

Under-excitation Limiting Overall Gain

-

0…1000

14

56

4

Real

UEL_Ki

Under-excitation Limiting Integral Gain

-

0…1000

15

60

4

Real

V_Match_Gain

Voltage Match Gain

-

0…1000

16

64

4

Real

kWHoursPreset

kW Hours Preset

-1 x 10

12

…1 x 10

12

17

68

4

Real

kVARHoursPreset

kVAR Hours Preset

-1 x 10

12

…1 x 10

12

18

72

4

Real

kVAHoursPreset

kVA Hours Preset

0…1 x 10

12

19

TIP

The last three elements are present only in the CGCM unit host firmware
revision 3.x or later.

Advertising