Troubleshooting Chapter 7

Protection

One or both CGCM units will not

operate as primary

Faulty wiring

Measure excitation enable input to

CGCM unit that will not act as

primary

Verify voltage is applied to

excitation enable input terminal

Check operation of external relay

and associated wiring for

redundancy relay and output

Correct excitation redundancy relay

operation

Check wiring of excitation +/- output

from CGCM unit

Correct excitation output wiring

Logix controller error

Check output to excitation enable

input (hardware and software)

Correct logic as required

Check logic to redundancy relay (if

applicable)

Correct logic as required

One CGCM unit has failed or is not

configured properly

Troubleshoot as non-redundant

CGCM unit

Correct or replace as needed

Table 32 - Redundancy

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

Table 33 - Protection

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

Loss of excitation current (40)

Wiring error

Check excitation output wiring

Correct wiring as required

Gains mis-adjusted

Check AVR gains

Calculate/adjust gains as required

Over-excitation voltage (59F)

Wiring error

Check excitation output wiring

Correct wiring as required

Gains mis-adjusted

Check AVR gains

Calculate/adjust gains as required

OEL limit exceeded

Check OEL operation

Correct as required

Generator over-voltage (59)

Rapid loss of large load

Gains mis-adjusted

Check AVR gains

Calculate/adjust gains as required

Generator under-voltage (27)

Over load

Wiring error

Check VT wiring. See Voltage

metering trouble shooting

Correct wiring as required

Loss of sensing (60FL)

Fuse open

Check VT fuses

Replace as required

Wiring error

Check for open connections and

phase rotation reversal

Correct wiring as required