Troubleshooting

Loss of permanent magnet

generator (PMG/Excitation power)

(27)

Supply circuit breaker trip/fuse open Check PMG supply. Measure with

voltmeter at CGCM unit PMG input

terminals

Correct/replace PMG input

protection as required

Wiring error

Check PMG supply. Measure with

voltmeter at CGCM unit PMG input

terminals

Correct wiring as required

PMG failure

Check PMG supply. Measure with

voltmeter at CGCM unit PMG input

terminals

Repair as required

Incorrect configuration

Check single-phase versus 3-phase

selection

Correct as required

Reverse var (40Q)

Under-excitation

Check UEL configuration if required, Correct as required

Incorrect operating mode selected

Check selected operating mode for

operating requirements

Select as appropriate

Over-frequency (81O)

Governor error

Correct as required

Under-frequency (81U)

Governor error

Correct as required

Reverse power (32R)

Governor error

Correct as required

Rotating diode monitor

Failed diode

Remove and test diodes

Replace diode

Incorrect configuration

Confirm test / set up of diode

monitor parameters with active

parameters

Correct as required

Insufficient number of fly back

diodes installed

Check number of external flyback

diodes installed at CGCM excitation

output if required

Install as required

Phase rotation error (47)

Wiring error

See troubleshooting voltage

metering

Correct wiring as required

Generator over-current (51)

Fault or large load condition

Incorrect configuration

Check configuration

Correct as required

Table 33 - Protection

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action