Over-excitation Voltage Protection

Over-current Protection

Under-voltage Protection

Over-voltage Protection

Loss of Sensing Protection

Attribute

Range

Increment

Pickup

1…200V DC

1V DC

Time delay

0.1…30 s

0.1 s

Attribute

Range

Increment

Accuracy

Pickup

10…320% of rated

generator current

1%

±2% rated current

Time delay

Characteristic inverse

per ANSI C50.13

configurable

0.1 s

Attribute

Range

Increment

Accuracy

Pickup

60…100% of rated

generator voltage

1%

±2% rated voltage

Time delay

0.1…300 s

±0.1 s

Attribute

Range

Increment

Accuracy

Pickup

100…140% of rated

generator voltage

1%

±2% rated voltage

Time delay

0.1…300 s

±0.1 s

Attribute

1407-CGCM

Pickup

See text description in Operation section of the manual for this item

Time delay

0.1 s for normal operation, 1 s during soft start