Validate and graph button – Updates the graph shown on the Current tab

to display the selected over-current characteristic curve. The specific curve
selected by the over-current time dial setting is displayed in black.

Related Parameters

GenRated_I
GenRated_V

Frequency Tab

The Frequency tab is used to configure the CGCM unit parameters related to the
over-frequency and under-frequency protection functions.

Over-frequency Setpoint - Establishes the generator over-frequency

setpoint. The tag OvrFreqSetpt in the configuration table stores this
parameter, expressed in Hz.

Over-frequency Delay - Establishes the amount of time in seconds that the

frequency must be above the over-frequency setpoint before the CGCM
unit annunciates the fault. This parameter is stored in tag
OvrFreqTimeDly

in the configuration table.

Under-frequency Setpoint - Establishes the generator under-frequency

setpoint. The tag UndrFreqSetpt in the configuration table stores this
parameter, expressed in Hz.

Under-frequency Delay - Establishes the amount of time in seconds that

the frequency must be below the under-frequency setpoint before the
CGCM unit annunciates the fault. This parameter is stored in tag
UndrFreqTimeDly

in the configuration table.