Chapter 4

CGCM Unit Configuration

Volts/Hz Tab

The Volts/Hz tab is used to configure the unit’s settings related to operation of
the Volts/Hz compensation function. The parameters define a curve, which
determines the Volts/Hz response.

Volts per Hertz Upper Knee Frequency - Establishes the frequency at

which the V/Hz characteristic starts to reduce the generator voltage as a
function of generator frequency. Tag VperHz_HiKneeFreq in the
configuration table stores this value, expressed in Hertz. The upper knee
frequency must be greater than the lower knee frequency.

Volts per Hertz Upper Slope - Establishes the rate at which the V/Hz

characteristic reduces the generator voltage as a function of generator
frequency between the upper and lower knee frequencies. Tag
VperHz_HiSlope

in the configuration table stores this value, expressed as

a number that reflects per unit change in voltage for each per unit change
in frequency.

Volts per Hertz Lower Knee Frequency - Establishes the frequency at

which the V/Hz characteristic starts to reduce the generator voltage at the
lower slope rate as a function of generator frequency. Tag
VperHz_LoKneeFreq

in the configuration table stores this value,

expressed in Hertz. The lower knee frequency must be less than the upper
knee frequency.