Acceptance Delay - Establishes the time that all sync parameters must be

continuously within their respective acceptance windows to permit closing
the breaker. The Configuration table tag SynchAcceptDly stores this
value, expressed in seconds.

Bus A Offsets

Voltage multiplier - Establishes a factor by which the Bus A voltage is

scaled during synchronization. It can be used to compensate for
transformer ratio differences between the generator and bus voltages. For
example, if the generator nominal voltage is 4160V and the nominal Bus A
voltage is 12,480V (each measured line-to-line), a voltage multiplier value
of 0.333 permits voltage matching during synchronization. Configuration
table tag BusA_V_Scaler stores this parameter.

Phase - Establishes an offset angle added to the measured Bus A phase

angle. It can be used to compensate for phase shift across transformers or
between delta and wye connected systems.

As an example, consider the system shown in

Voltage and Current

Connection for Four-wire Wye Bus and Two (or three) Transformer Delta
Generator System

on

page 24

.

When a generator with three-wire (delta) metering is synchronized to a
bus with four-wire (wye) metering, set the phase offset to 30° to
compensate for the 30° lag between the delta and wye systems.
Configuration table tag BusA_PhOffset stores this parameter, expressed
in degrees.

Bus B Offsets

Voltage multiplier - Establishes a factor by which the Bus B voltage is

scaled during synchronization. It can be used to compensate for
transformer ratio differences between the generator and bus voltages.
Configuration table tag BusB_V_Scaler stores this parameter.

Phase - Establishes an offset angle added to the measured Bus B phase

angle. It can be used to compensate for phase shift across transformers or
between delta and wye connected systems. Configuration table tag
BusB_PhOffset

stores this parameter, expressed in degrees.