Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

221

Detailed CGCM Unit Tag Descriptions Appendix E

Reverse Power Protection Outputs from the CGCM Unit

• RevPwrFlt - This tag is used to communicate the occurrence of a Reverse

Power Fault to the host Logix controller. When this tag is a 1, it indicates
that a fault has occurred. The tag is latched until the host Logix controller
resets it by setting the FltReset tag.

Rotating Diode Monitor Inputs to the CGCM Unit

• RotDiodeFltOutEn - When this tag is a 1 in the configuration, and a

Shorted or Open Rotating Diode Fault occurs, the Fault Relay is
energized. When this tag is a 0 in the configuration, a these conditions has
no effect on the Fault Relay.

• OpenDiodeMonitorLevel - This tag sets the percent ripple at which the

rotating diode monitor alarm announces when an open diode condition
occurs.

• ShortedDiodeMonitorLevel - This tag sets the percent ripple at which

the rotating diode monitor alarm announces when a shorted diode
condition occurs.

• DiodeMonitorTimeDly - This tag sets the amount of time the CGCM

unit takes before the CGCM unit announces the rotating diodes have an
anomaly.

• MainPole - This tag sets the number of poles of the main field of the

generator.

• ExciterPole - This tag sets the number of poles of the exciter field of the

generator.

Rotating Diode Monitor Outputs from the CGCM Unit

• RotDiodeFlt - This tag is used to communicate the occurrence of a

Shorted or Open Rotating Diode Fault to the host Logix controller. When
this tag is a 1, it indicates that a fault has occurred. The tag is latched until
the host Logix controller resets it by setting the FltReset tag.

• ShortedRotDiodeFlt – This tag indicates that a Shorted Rotating Diode

Fault caused the RotDiodeFlt tag to be set.

• OpenRotDiodeFlt - This tag indicates that an Open Rotating Diode

Fault caused the RotDiodeFlt tag to be set.

Phase Rotation Check Inputs to the CGCM Unit

• PhRotFltOutEn - When this tag is a 1 in the configuration, and a Phase

Rotation Fault occurs the Fault Relay is energized. When this tag is a 0 in
the configuration, a Phase Rotation Fault has no effect on the Fault Relay.