Troubleshooting Chapter 7

Table 21 - Reactive Power Control - PF

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

Power Factor not at PF setpoint

PF not enabled

Check input tag PF_Ened

If not enabled, select appropriate

modes of operation to enable PF

mode

Gain misadjusted

Observe response of PF to changes

in PF setpoint

If a response is slow, increase gain

Diode failure

Use diode monitor if previously

configured or measure/check diodes

Replace as required

Excitation limiting active

Check UEL/OEL active input

Correct UEL/OEL configuration or

change operating point

Power Factor unstable/erratic

Gain misadjusted

Observe response of PF to changes

in PF setpoint

Adjust until a stable response is

observed

Wiring Error

Check stability in other control mode

such as Droop

If stable in other mode, see above.

Otherwise, check field output wiring

and VT/CT input wiring

Table 22 - Reactive Power Control - VAR

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

VARs not at VAR setpoint

VAR not enabled

Check input tag VAR_Ened

If not enabled, select appropriate

modes of operation to enable VAR

mode

Gain misadjusted

Observe response of VAR to

changes in VAR setpoint

If a response is slow, increase gain

Diode failure

Use diode monitor if previously

configured or measure/check diodes

Replace as required

Excitation limiting active

Check UEL/OEL active input

Correct UEL/OEL configuration or

change operating point

VARs unstable/erratic

Gain misadjusted

Observe response of VAR to

changes in VAR setpoint

Adjust until a stable response is

observed

Wiring Error

Check stability in other control mode

such as Droop

If stable in other mode, see above.

Otherwise, check field output wiring

and VT/CT input wiring