Specifications

Remote Excitation Enable Input

Open Collector Outputs (fault relay and redundancy relay)

Field Output

Attribute

1407-CGCM

Voltage rating

24V DC nom

Input impedance

5.6K 

Logical high voltage, min

18V DC

Logical low voltage, max

5V DC

Attribute

1407-CGCM

Voltage rating

24V DC nom

Voltage range

18…30V DC

Rated current, max

500 mA

Attribute

1407-CGCM

Continuous voltage

32, 63, 125V DC

(1)

(1) Available output voltage is dependent on magnitude of excitation power input voltage.

Continuous current

15 A DC

10-second forcing voltage

50, 100, or 200V DC

10-second forcing current

30 A DC

Field resistance, min

32V DC

63V DC

125V DC

2.13 

4.2 

8.3 