Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual
Page 200
Advertising
200
Rockwell Automation Publication 1407-UM001G-EN-P - April 2013
Appendix D
Specifications
Remote Excitation Enable Input
Open Collector Outputs (fault relay and redundancy relay)
Field Output
Attribute
1407-CGCM
Voltage rating
24V DC nom
Input impedance
5.6K
Logical high voltage, min
18V DC
Logical low voltage, max
5V DC
Attribute
1407-CGCM
Voltage rating
24V DC nom
Voltage range
18…30V DC
Rated current, max
500 mA
Attribute
1407-CGCM
Continuous voltage
32, 63, 125V DC
(1)
(1) Available output voltage is dependent on magnitude of excitation power input voltage.
Continuous current
15 A DC
10-second forcing voltage
50, 100, or 200V DC
10-second forcing current
30 A DC
Field resistance, min
32V DC
63V DC
125V DC
2.13
4.2
8.3