Generator over-voltage outputs from the cgcm unit, Inputs to the cgcm unit, Generator under-voltage outputs from the cgcm unit – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 218: Loss of sensing inputs to the cgcm unit, Loss of sensing outputs from the cgcm unit

Advertising
background image

218

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Appendix E

Detailed CGCM Unit Tag Descriptions

Generator Over-voltage Outputs from the CGCM Unit

• Ovr_V_Flt – This tag is used to communicate the occurrence of an

Over-voltage Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.

Inputs to the CGCM Unit

• Undr_V_FltOutEn - When this tag is a 1 in the configuration, and an

Under-voltage Fault occurs (as defined by the Undr_V_Setpt tag), the
Fault Relay is energized. When this tag is a 0 in the configuration, an
Under-voltage Condition has no effect on the Fault Relay.

• Undr_V_Setpt - This tag configures the generator under-voltage setpoint

that the CGCM unit uses to recognize an under-voltage condition. When
the condition occurs, the CGCM unit starts timing toward a trip.

• Undr_V_TimeDly - This setting establishes the time to trip the unit once

the generator Under-voltage Setpoint has been exceeded.

• EngineIdle – Setting this tag to 1 enables Soft Start mode and disables the

under-frequency, under-voltage, and Loss of PMG protections until the
generator is at rated speed.

Generator Under-voltage Outputs from the CGCM Unit

• Undr_V_Flt - This tag is used to communicate the occurrence of an

Under-voltage Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.

Loss of Sensing Inputs to the CGCM Unit

• LossSensingFltOutEn - When this tag is a 1 in the configuration, and a

Loss of Sensing Fault occurs the Fault Relay is energized. When this tag is a
0 in the configuration, a Loss of Sensing Condition has no effect on the
Fault Relay.

Loss of Sensing Outputs from the CGCM Unit

• LossSensingFlt - This tag is used to communicate the occurrence of a Loss

of Sensing Fault to the host Logix controller. When this tag is a 1, it
indicates that a fault has occurred. The tag is latched until the host Logix
controller resets it by setting the FltReset tag.