Time over-current characteristic curve graphs – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 166

Advertising
background image

166

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Appendix A

Time Over-current Characteristic Curves

Time Over-current
Characteristic Curve
Graphs

The following illustrations show the characteristic curves of the CGCM.
Equivalent time dial settings were calculated at a value of five times pickup.

The

Characteristic Curve Cross-Reference

table cross-references each curve to

existing electromechanical relay characteristics.

Table 34 - 51P and 51N Time Characteristic Curve Constants

Curve
Selection

Curve Name

Trip Characteristic Constants

Reset

A

B

C

N

K

R

1

S, Short Inverse

0.2663

0.03393

1.000

1.2969

0.028

0.5000

2

S2, Short Inverse

0.0286

0.02080

1.000

0.9844

0.028

0.0940

3

L1, Long Inverse

5.6143

2.18592

1.000

1.000

0.028

15.750

4

L2, Long Inverse

2.3955

0.00000

1.000

0.3125

0.028

7.8001

5

D, Definite Time

0.4797

0.21359

1.000

1.5625

0.028

0.8750

6

M, Moderately Inverse

0.3022

0.12840

1.000

0.5000

0.028

1.7500

7

I, Inverse Time

8.9341

0.17966

1.000

2.0938

0.028

9.0000

8

Inverse Time

0.2747

0.10426

1.000

0.4375

0.028

0.8868

9

V, Very Inverse

5.4678

0.10814

1.000

2.0469

0.028

5.5000

10

V2, Very Inverse

4.4309

0.09910

1.000

1.9531

0.028

5.8231

11

Extremely Inverse

7.7624

0.02758

1.000

2.0938

0.028

7.7500

12

E2, Extremely Inverse

4.9883

0.01290

1.000

2.0469

0.028

4.7742

13

Standard Inverse

0.01414

0.00000

1.000

0.0200

0.028

2.0000

14

B, Very Inverse (I

2

t)

1.4636

0.00000

1.000

1.0469

0.028

3.2500

15

Extremely Inverse (I

2

t)

8.2506

0.00000

1.000

2.0469

0.028

8.0000

16

Long Time Inverse (I

2

t)

12.1212

0.00000

1.000

1.0000

0.028

29.0000

17

Fixed Time

0.0000

1.00000

1.000

0.0000

0.028

1.0000

Advertising