Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 94

Advertising
background image

94

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 4

CGCM Unit Configuration

Power Factor Traverse Rate - Sets tag PF_Traverse_Rate in the

Configuration table. This parameter determines the time measured in
seconds for the PF setpoint to move from 0.50 lagging to 0.50 leading or
vice versa. It determines how fast the regulator changes the power factor
setpoint from the tracking value to the operating setpoint when the
Regulator Operating mode changes to PF.

VAR Control Traverse Rate - Sets tag VAR_Traverse_Rate in the

Configuration table. This parameter determines the time measured in
seconds for the setpoint to move from zero to the rated generator KVA. It
determines how fast the regulator changes the VAR setpoint from the
tracking value to the operating setpoint when the Regulator Operating
mode changes to VAR.

Manual Control (FCR) Traverse Rate - Sets tag FCR_Traverse_Rate in

the Configuration table. This parameter determines the time measured in
seconds for the setpoint to move from zero to the rated exciter current. It
determines how fast the regulator changes the field current setpoint from
the tracking value to the operating setpoint when the Regulator Operating
mode changes to FCR.

The following diagram shows the function of internal tracking and traverse rates
on a switch from VAR to PF operating modes.

Figure 40 - Internal Tracking and Traverse Rates

VAR Mode

PF Mode

Excitation Current

VARs

Power Factor

Generator Voltage

PF Mode Setpoint

PF Mode Internal

Tracking Setpoint =

Measured PF

PF Mode Traverse Rate

Determines Transition to New

Mode's Operating Point

VAR Internal

Tracking Setpoint

FCR Internal

Tracking Setpoint

PF is New

Process Variable

VARs are Old Process

Variable