Troubleshooting Chapter 7

Voltage output is less than setpoint

AVR not selected/enabled

Check excitation enable (hardware

and software) and AVR select

Correct Logix controller logic or I/O

as required

Wiring error

Check wiring for excitation enable,

excitation current output, VT inputs,

fuses open, grounding, and

PMG/supply

Correct wiring as required

Insufficient supply power

Measure Voltage at CGCM unit

PMG/supply input terminals

Correct supply anomaly if

insufficient voltage is measured

Measure generator residual voltage

(shunt excitation)

If less than 10V AC, consult

generator manufacturer’s

documentation and flash the

generator field

Generator not up to rated speed

Check generator speed

Increase generator speed to rated

speed

Correct condition preventing rated

speed from being attained

Field resistance too great

Disconnect field current outputs at

CGCM unit and measure load

resistance

Correct/verify load resistance is

within CGCM unit capability

Gain mis-adjusted

Check gains entered into CGCM unit

configuration

Calculate/adjust as required

Excitation limiting active

Check OEL active input

Correct OEL configuration or change

operating point

Droop compensation is driving down

the voltage

Check Droop Enable

Adjust/disable droop compensation

Table 20 - Excitation Control - AVR

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action