Data table – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 136

Advertising
background image

136

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 6

CGCM Unit Software Interface

Data Table

Table 10 - Output (scheduled write) Data Table, Assembly Instance 1

Byte

Size
in
Bytes

Type

Bits

Tag Name

Description

Units

Range

0

1

Bool

0

RevVARFltOutEn

Reverse VAR Fault Output Enable -

0=Disabled,

1=Enabled

Bool

1

RevPwrFltOutEn

Reverse Power Fault Output

Enable

Bool

2

OvrExcFltOutEn

Over-excitation Fault Output

Enable

Bool

3

Ovr_I_FltOutEn

Over-current Fault Output Enable

Bool

4

Undr_V_FltOutEn

Under-voltage Fault Output

Enable

Bool

5

Ovr_V_FltOutEn

Over-voltage Fault Output Enable

Bool

6

UndrFreqFltOutEn

Under-frequency Fault Output

Enable

Bool

7

OvrFreqFltOutEn

Over-frequency Fault Output

Enable

1

1

Bool

0

Spare1

-

-

Bool

1

LossExcFltOutEn

Loss Excitation Fault Output

Enable

0=Disabled,

1=Enabled

Bool

2

OEL_En

Over-excitation Limiting Enable

Bool

3

UEL_En

Under-excitation Limiting Enable

Bool

4

LossSensingFltOutEn

Loss Sensing Fault Output Enable

Bool

5

LossPMGFLtOutEn

Loss Permanent Magnet

Generator Fault Output Enable

Bool

6

RotDiodeFltOutEn

Rotation Diode Fault Output

Enable

Bool

7

PhRotFltOutEn

Phase Rotation Fault Output

Enable

2

1

Bool

0

Spare2

-

-

Bool

1

Spare3

Bool

2

EngineIdle

Engine Idle

0=False, 1=True

Bool

3

Spare4

Bool

4

PF_VAR_Select

Power Factor/VAR Select

0=PF, 1=VAR

Bool

5

PF_VAR_En

Power Factor/VAR Enable

0=Disabled,

1=Enabled

Bool

6

AVR_FCR_Select

Automatic Voltage

Regulator/Field Current Regulator

Select

0=AVR, 1=FCR

Bool

7

FltReset

Fault Reset

0=De-assert,

1=Assert